Elektromontaż 1 Katowice S.A.
ul. Słoneczna 50
40-135 Katowice
Tel: +48 32 3593 100
Fax: +48 32 2583 525
|
Basic technical data SIVACON 8PT - with busbar on the top of the cubicle
|
|||
|
Standards and specifications
|
Type-tested low-voltage
switchgear and control gear assembly (TTA) Testing of response to internal faults (arcing faults) |
PE-EN 60439-1, IEC 60439-1, DIN EN 60439-1(VDE 0660 Teil 500)
IEC 61641, VDE 0660 part 500, Supplement 2 |
|
|
Creepage distances
and clearances |
Rated impulse withstand voltage
(Uimp) |
8kV
|
|
|
Overvoltage category
|
III
|
||
|
Pollution degree
|
3
|
||
|
Rated insulation voltage (Ui)
|
|
1000V
|
|
|
Rated operational voltage (Ue)
|
|
up to 690V
|
|
|
Rated currents (In)
Busbars (3-pole and 4-pole)
|
Main horizontal busbars
|
Rated current
|
up to 7400A
|
|
Rated peak withstand current (Ipk)
|
up to 375kA
|
||
|
Rated short-time withstand current (Icw)
|
up to 150kA, 1s
up to 120kA, 3s |
||
|
Vertical busbars
for circuit breakers |
Rated current
|
up to 6300A
|
|
|
Rated peak withstand current (Ipk)
|
up to 250kA
|
||
|
Rated short-time withstand current (Icw)
|
up to 100kA, 1s
up to 80kA, 3s |
||
|
Vertical busbars
for fixed-mounted design |
Rated current
|
do 1400A
|
|
|
Rated peak withstand current (Ipk)
|
up to 163kA
|
||
|
Rated short-time withstand current (Icw)
|
up to 65kA*, 1s
up to 50kA, 3s |
||
|
Vertical busbars
for in-line plug-in design (3NJ6) |
Rated current
|
up to 2100A
|
|
|
Rated peak withstand current (Ipk)
|
up to 110kA
|
||
|
Rated short-time withstand current (Icw)
|
up to 50kA*, 1s
|
||
|
Switchgear rated currents
|
|
Circuit breakers
|
up to 6300A
|
|
|
Outgoing feeders
|
up to 630A
|
|
|
Internal separation
|
Form 1 to Form 4
|
IEC 60439-1, Section 7.7, DIN EN 60439-1
|
|
|
Surface treatment
|
Frame parts
|
Galvanized/powder-coated/wet-painted
|
|
|
Enclosure
|
Galvanized/powder-coated/wet-painted
|
||
|
Doors
|
Powder-coated/wet-painted
|
||
|
Degree of protection
|
To IEC 60529, EN 60529
|
IP30 to IP54
|
|
|
Dimensions
|
|
Height:
|
2200mm
|
|
Height with busbar top unit:
|
2600mm
|
||
|
Width:
|
400, 600, 800,
1000, 1200mm |
||
|
Depth:
|
600, 800,
1000, 1200mm |
||
* Rated conditional short-circuit current lec up to 100 kA